MODEL |
ZEB-OU10KE16 |
|
Phase |
1-phase in / 1-phase out |
|
Capacity |
10000 VA 8000W |
|
INPUT |
|
|
Nominal Voltage |
208/220/230/240VAC |
|
Voltage Range |
110-300 VAC (Based on load at 50%) 176-300 VAC (Based on load at 100%) |
|
Frequency Range |
46~54 Hz or 56~64 Hz |
|
Power Factor |
≥0.99 @ 100% Load |
|
OUTPUT |
|
|
Output Voltage |
208/220/230/240VAC |
|
AC Voltage Regulation (Batt. Mode) |
± 1% |
|
Frequency Range (Synchronized Range) |
46~54Hz |
|
Frequency Range (Batt. Mode) |
50 Hz ± 0.1 Hz |
|
Current Crest Ratio |
3:1 (max.) |
|
Harmonic Distortion |
≦ 3 % THD (Linear Load) |
|
|
≦ 5 % THD (Non-linear Load |
|
Transfer Time |
AC Mode to Batt. Mode : Zero |
|
|
Inverter to Bypass : Zero |
|
Waveform (Batt. Mode) |
Pure Sine wave |
|
EFFICIENCY |
|
|
AC Mode |
93.00% |
|
BATT Mode |
91.00% |
|
BATTERY |
|
|
Numbers |
16 ~ 20 (Adjustable)* |
|
Typical Recharge Time |
9hrs recover to 90% capacity |
|
Battery Type |
SMF/VRLA |
|
Charging Current (max.) |
1A/2A/4A/6A (Adjustable, 6A is only available for 16pcs batteries |
|
Charging Voltage |
13.65 x N (N-Number of battery |
|
INDICATORS |
|
|
LCD Display |
UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions |
|
ALARM |
|
|
Battery Mode |
Sounding every 4 seconds |
|
Low Battery |
Sounding every second |
|
Overload |
Sounding twice every second |
|
Fault |
Continuously sounding |
|
PHYSICAL |
|
|
Dimension,DxWxH (mm) |
442 x 190 x 318 |
|
Net Weight (kgs) |
16 |
|
ENVIRONMENT |
|
|
Operation Humidity |
0-95% RH @ 0-40°C (non-condensing |
|
Noise Leve |
Less than 58dB @ 1 Meter |
|
MANAGEMENT |
|
|
Smart RS-232 / USB |
Supports Windows 2 2000/2003/XP/Vista/2008, Windows2 7/8/10, Linux and MAC |
|
Optional SNMP |
Power management from SNMP manager and web browser |